Calculators / Ventilation and power
Stove outlet and range circuit: what size?
Pick the range, or put in the kW from its rating plate, and tell us what’s at the wall. You get the NEC figure, what the maker asks for, the breaker, wire and outlet, and whether the circuit there now is enough.
Updated · How we check our numbers
Your circuit works
40 A circuit, 8 AWG
The NEC counts this range as 8.4 kW, 35 A at 240 V, on a 40 A breaker. That’s 8 AWG copper NM-B on a 40 A breaker; your 40 A circuit covers it.
- NEC demand
- 8.4 kW35 A at 240 V
- Breaker
- 40 Adouble-pole, 240 V
- Copper wire
- 8 AWGNM-B cable
- Receptacle
- NEMA 14-50R4-wire, as LG names it
Estimate for planning only, not professional advice. Check the manufacturer’s instructions, your local code and a licensed professional before you buy, build or install. Use at your own risk. Terms.
What size wire for the range (on Spec My Garage)40 A at 240 V, with your run length
Can the panel take it?The NEC load calc for adding a range
Size the hoodCFM, width and duct
13 kW − 12 = 1 kW over → 1 (a half kW or more rounds up) × 5% → 8 kW × 1.1 = 8.4 kW
8.4 kW × 1,000 ÷ 240 V = 35 A → 40 A breaker (40 A minimum)
maker: 40 A
circuit = the bigger = 40 A → 8 AWG copper NM-B (60 °C column, 240.4(D))
Bars run from 0 A. The breaker is the bigger of the NEC figure and the maker’s; the wire has to carry the breaker.
The checks
- NEC demand load13 kW range → 8 kW + 1 × 5% = 8.4 kW35 A → 40 A
8.4 kW ÷ 240 V = 35 A. A range of 8¾ kW or more needs at least a 40 A circuit (210.19(A)(3)).
- What LG LSEL6335 asks for40 A minimum at 240 V40 A
“Minimum Circuit Rating 40 Amp”, “kW Rating at 240V 13.0 kW”, “4-Wire (14-50R) / 3-Wire (10-50R)”.
- Circuit there now40 ASame size
The circuit you have carries it.
- ReceptacleNEMA 14-50 (4 slots, 50 A)4-wire
The 4-wire range receptacle LG names (14-50R). Use a 4-wire cord rated for the circuit: GE asks for a 40 A cord; Whirlpool a 50 A cord kit on a 50 A circuit.
A new 240 V circuit takes a permit in most towns, and many want a licensed electrician to run it. Your local code has the final say. Use this to plan and price the job, then have it inspected.
The kW on the rating plate and the installation instructions have the final say. GE puts the plate on the oven frame or the drawer frame; Whirlpool behind the oven door, top right.
A household range is sized by Table 220.55, not at 125% as a continuous load, so the wire carries the breaker as is.
In an apartment on 208 V the same range draws less: LG rates the LSEL6335 at 13.0 kW at 240 V and 9.8 kW at 208 V. GE and Whirlpool allow 120/208 V.
How we work it out
The NEC figure. The electrical code doesn’t count a household range at its full nameplate. Table 220.55 gives one range rated over 8¾ kW and up to 12 kW a demand load of 8 kW (Column C). Over 12 kW, Note 1 adds 5% for each kW, or major fraction, past 12; Mike Holt’s worked example takes a 14 kW range to 8 kW × 1.10 = 8.8 kW. A range of 8¾ kW or more needs at least a 40 A circuit (210.19(A)(3)).
demand = 8 kW × (1 + 5% × kW over 12, a half kW rounding up)
amps = demand kW × 1,000 ÷ 240 V → the next breaker size up, 40 A at least
| Nameplate | NEC demand | Amps | Breaker |
|---|---|---|---|
| 8 kW | 8 kW | 33.3 A | 35 A |
| 10 kW | 8 kW | 33.3 A | 40 A |
| 12 kW | 8 kW | 33.3 A | 40 A |
| 13 kW | 8.4 kW | 35 A | 40 A |
| 14 kW | 8.8 kW | 36.7 A | 40 A |
| 15 kW | 9.2 kW | 38.3 A | 40 A |
| 16 kW | 9.6 kW | 40 A | 40 A |
| 18 kW | 10.4 kW | 43.3 A | 45 A |
| 20 kW | 11.2 kW | 46.7 A | 50 A |
| 22 kW | 12 kW | 50 A | 50 A |
What the maker asks for. The NEC figure is the least the code allows; the range’s instructions can ask for more, and the bigger one sets the circuit. GE asks for a “40 amp (minimum) branch circuit” on its 30 in electric ranges. Whirlpool’s chart puts 8.8 to 16.5 kW on 40 or 50 A and 16.6 to 22.5 kW on 50 A. Pro-style induction ranges from Wolf, Thermador, BlueStar and ZLINE all name 50 A. The circuit each model in the calculator asks for:
- LG LSEL6335 (30 in slide-in electric): 40 A at 240 V.
- GE free-standing or front control electric (30 in): 40 A at 240 V.
- Samsung NE63A6511SS (30 in electric): 40 A at 240 V.
- Whirlpool WEE515S0L / WEC310S0L (30 in electric): by kW, from the chart.
- Wolf IR36550/S/T: 50 A at 240 V.
- Thermador PRI36LBHU: 50 A at 240 V.
- BlueStar 36 in Platinum induction: 50 A at 240 V.
- ZLINE SINRB-36: 50 A at 240 V.
- Wolf DF36650: 30 A at 240 V.
- Wolf DF48650G: 50 A at 240 V.
- Thermador PRD366WHU: 30 A at 240 V.
- Thermador PRD486WDHU: 50 A at 240 V.
- BlueStar 36 in dual fuel: 40 A at 240 V.
- ZLINE MDR36: 25 A at 240 V.
- ZLINE MDR48: 35 A at 240 V.
- Bosch HDS8657U: 20 A at 240 V.
Wire. The wire has to carry the breaker. Copper NM-B cable is held to the 60 °C column: 8 AWG for 40 A, 6 AWG for 50 A. THHN in conduit uses 75 °C: 8 AWG carries 50 A. For a long run, check the voltage drop with the wire size calculator on Spec My Garage.
The outlet. LG names a 4-wire NEMA 14-50R or a 3-wire 10-50R. GE: since January 1, 1996 the NEC “requires that new construction (not existing) utilize a 4-conductor connection to an electric range”, and a 4-wire cord wherever local code doesn’t allow grounding through the neutral. A 30 A dryer outlet (14-30 or 10-30) isn’t a range outlet.
Gas ranges need a 120 V outlet, not a 240 V one: Whirlpool asks for a 15 A circuit, ideally serving only the range, and a ¾ in rigid gas supply (½ in minimum on LP), at 6 to 14 in of water column on natural gas. Size the pipe with the gas line calculator.
A new 240 V circuit takes a permit in most towns, and many want a licensed electrician. Swapping gas for induction? The induction swap check adds the range to your panel’s load calc. Pro-style ranges and their hoods: 36 and 48 inch ranges and the range hood sizer.
Left out. Frigidaire’s own spec sheets didn’t come up for our reader (only retailer copies), nor did GE’s gas range instructions; the NEC’s Column A and B percentages for ranges under 8¾ kW aren’t in the articles we read, so under 8¾ kW we go by the nameplate. Separate cooktops and wall ovens aren’t covered.
Where the numbers come from
- Mike Holt: Illustrated Guide to Exam Preparation, 2017 NEC (Table 220.55, Note 1, worked range example)
- Mike Holt, EC&M: Code Q&A, household ranges and cooking appliances (210.19(A)(3), 40 A)
- Mike Holt, EC&M: Code Quandaries (16 kW range is 9.6 kW, 40 A at 240 V)
- Mike Holt, EC&M: multifamily calculations (a major fraction of a kW rounds up)
- Mike Holt, EC&M: Code Q&A, sizing branch circuits (ranges by Table 220.55)
- GE Appliances: free-standing and front control electric range installation instructions (31-2000911 Rev. 2)
- Whirlpool: front control electric range dimension guide W11508843A (range rating chart)
- Whirlpool: 30 in slide-in gas range dimension guide W11508844A (gas and 120 V)
- LG: LSEL6335 builder spec sheet (13.0 kW, 40 A, 14-50R / 10-50R)
- Samsung: NE63A6511SS spec sheet (240V/208V/60 Hz/40A)
Power
The range and hood
More calculators
- Range hood sizerWhat CFM, width and duct do I need?
- Induction swapCan my panel run an induction range?
- Induction cookware checkWill my pans work on induction?
- Microwave cabinet fitWill a microwave fit over my range, in a drawer or built in?
- Island fitWill an island fit and leave room to walk?
- Island seatingHow many stools, and what height?
- Dining room fitWill the table fit, and how many does it seat?
- Pendant heightHow high over the island?