Stove outlet and range circuit: what size?

Pick the range, or put in the kW from its rating plate, and tell us what’s at the wall. You get the NEC figure, what the maker asks for, the breaker, wire and outlet, and whether the circuit there now is enough.

Updated · How we check our numbers

These are example numbers. Put in yours.

The range

Range
kW

kW at 240 V, on the rating plate or the spec sheet. Optional for a model that states one.

At the wall now

Range breaker now

A double breaker marked 30, 40 or 50.

Outlet behind the range
New wire would be

Your circuit works

40 A circuit, 8 AWG

The NEC counts this range as 8.4 kW, 35 A at 240 V, on a 40 A breaker. That’s 8 AWG copper NM-B on a 40 A breaker; your 40 A circuit covers it.

NEC demand
8.4 kW35 A at 240 V
Breaker
40 Adouble-pole, 240 V
Copper wire
8 AWGNM-B cable
Receptacle
NEMA 14-50R4-wire, as LG names it

Estimate for planning only, not professional advice. Check the manufacturer’s instructions, your local code and a licensed professional before you buy, build or install. Use at your own risk. Terms.

What size wire for the range (on Spec My Garage)40 A at 240 V, with your run length

Can the panel take it?The NEC load calc for adding a range

Size the hoodCFM, width and duct

13 kW − 12 = 1 kW over → 1 (a half kW or more rounds up) × 5% → 8 kW × 1.1 = 8.4 kW

8.4 kW × 1,000 ÷ 240 V = 35 A → 40 A breaker (40 A minimum)

maker: 40 A

circuit = the bigger = 40 A → 8 AWG copper NM-B (60 °C column, 240.4(D))

Amps, to scale
Nameplate: 54.2 ANEC demand: 35 AMaker asks: 40 ABreaker: 40 AThere now: 40 A

Bars run from 0 A. The breaker is the bigger of the NEC figure and the maker’s; the wire has to carry the breaker.

The checks

  • NEC demand load13 kW range → 8 kW + 1 × 5% = 8.4 kW
    35 A → 40 A

    8.4 kW ÷ 240 V = 35 A. A range of 8¾ kW or more needs at least a 40 A circuit (210.19(A)(3)).

  • What LG LSEL6335 asks for40 A minimum at 240 V
    40 A

    “Minimum Circuit Rating 40 Amp”, “kW Rating at 240V 13.0 kW”, “4-Wire (14-50R) / 3-Wire (10-50R)”.

  • Circuit there now40 A
    Same size

    The circuit you have carries it.

  • ReceptacleNEMA 14-50 (4 slots, 50 A)
    4-wire

    The 4-wire range receptacle LG names (14-50R). Use a 4-wire cord rated for the circuit: GE asks for a 40 A cord; Whirlpool a 50 A cord kit on a 50 A circuit.

Permit

A new 240 V circuit takes a permit in most towns, and many want a licensed electrician to run it. Your local code has the final say. Use this to plan and price the job, then have it inspected.

Rating plate

The kW on the rating plate and the installation instructions have the final say. GE puts the plate on the oven frame or the drawer frame; Whirlpool behind the oven door, top right.

Not continuous

A household range is sized by Table 220.55, not at 125% as a continuous load, so the wire carries the breaker as is.

208 V

In an apartment on 208 V the same range draws less: LG rates the LSEL6335 at 13.0 kW at 240 V and 9.8 kW at 208 V. GE and Whirlpool allow 120/208 V.

How we work it out

The NEC figure. The electrical code doesn’t count a household range at its full nameplate. Table 220.55 gives one range rated over 8¾ kW and up to 12 kW a demand load of 8 kW (Column C). Over 12 kW, Note 1 adds 5% for each kW, or major fraction, past 12; Mike Holt’s worked example takes a 14 kW range to 8 kW × 1.10 = 8.8 kW. A range of 8¾ kW or more needs at least a 40 A circuit (210.19(A)(3)).

demand = 8 kW × (1 + 5% × kW over 12, a half kW rounding up)

amps = demand kW × 1,000 ÷ 240 V → the next breaker size up, 40 A at least

One range on 240 V, Table 220.55 Column C and Note 1
NameplateNEC demandAmpsBreaker
8 kW8 kW33.3 A35 A
10 kW8 kW33.3 A40 A
12 kW8 kW33.3 A40 A
13 kW8.4 kW35 A40 A
14 kW8.8 kW36.7 A40 A
15 kW9.2 kW38.3 A40 A
16 kW9.6 kW40 A40 A
18 kW10.4 kW43.3 A45 A
20 kW11.2 kW46.7 A50 A
22 kW12 kW50 A50 A

What the maker asks for. The NEC figure is the least the code allows; the range’s instructions can ask for more, and the bigger one sets the circuit. GE asks for a “40 amp (minimum) branch circuit” on its 30 in electric ranges. Whirlpool’s chart puts 8.8 to 16.5 kW on 40 or 50 A and 16.6 to 22.5 kW on 50 A. Pro-style induction ranges from Wolf, Thermador, BlueStar and ZLINE all name 50 A. The circuit each model in the calculator asks for:

  • LG LSEL6335 (30 in slide-in electric): 40 A at 240 V.
  • GE free-standing or front control electric (30 in): 40 A at 240 V.
  • Samsung NE63A6511SS (30 in electric): 40 A at 240 V.
  • Whirlpool WEE515S0L / WEC310S0L (30 in electric): by kW, from the chart.
  • Wolf IR36550/S/T: 50 A at 240 V.
  • Thermador PRI36LBHU: 50 A at 240 V.
  • BlueStar 36 in Platinum induction: 50 A at 240 V.
  • ZLINE SINRB-36: 50 A at 240 V.
  • Wolf DF36650: 30 A at 240 V.
  • Wolf DF48650G: 50 A at 240 V.
  • Thermador PRD366WHU: 30 A at 240 V.
  • Thermador PRD486WDHU: 50 A at 240 V.
  • BlueStar 36 in dual fuel: 40 A at 240 V.
  • ZLINE MDR36: 25 A at 240 V.
  • ZLINE MDR48: 35 A at 240 V.
  • Bosch HDS8657U: 20 A at 240 V.

Wire. The wire has to carry the breaker. Copper NM-B cable is held to the 60 °C column: 8 AWG for 40 A, 6 AWG for 50 A. THHN in conduit uses 75 °C: 8 AWG carries 50 A. For a long run, check the voltage drop with the wire size calculator on Spec My Garage.

The outlet. LG names a 4-wire NEMA 14-50R or a 3-wire 10-50R. GE: since January 1, 1996 the NEC “requires that new construction (not existing) utilize a 4-conductor connection to an electric range”, and a 4-wire cord wherever local code doesn’t allow grounding through the neutral. A 30 A dryer outlet (14-30 or 10-30) isn’t a range outlet.

Gas ranges need a 120 V outlet, not a 240 V one: Whirlpool asks for a 15 A circuit, ideally serving only the range, and a ¾ in rigid gas supply (½ in minimum on LP), at 6 to 14 in of water column on natural gas. Size the pipe with the gas line calculator.

A new 240 V circuit takes a permit in most towns, and many want a licensed electrician. Swapping gas for induction? The induction swap check adds the range to your panel’s load calc. Pro-style ranges and their hoods: 36 and 48 inch ranges and the range hood sizer.

Left out. Frigidaire’s own spec sheets didn’t come up for our reader (only retailer copies), nor did GE’s gas range instructions; the NEC’s Column A and B percentages for ranges under 8¾ kW aren’t in the articles we read, so under 8¾ kW we go by the nameplate. Separate cooktops and wall ovens aren’t covered.