Calculators / Ventilation and power
Can your panel run an induction range?
Pick the range and tell us what's at the wall now. Then a few questions about your house. You'll know if the circuit works and if the panel has room.
Your panel can run it
40 A circuit, 60 A to spare
The circuit you have works, and the panel has 60 A to spare.
- Range
- 12 kW40 A circuit
- At the range now
- 40 A
- Panel
- 90 Aof 150 A
circuit = 12 kW × 1000 ÷ 240 V × 80% = 40 A → 40 A breaker
lights and plugs = 1800 sq ft × 3 VA = 5.4 kVA
house loads = 5.4 kVA + kitchen and laundry circuits 4.5 kVA + appliances 7.5 kVA + induction range 12 kVA = 29.4 kVA
counted = 8 kVA + (29.4 kVA − 8 kVA) × 40% = 16.6 kVA
with heat and AC at 100% = 16.6 kVA + 5 kVA = 21.6 kVA
load = 21.6 kVA ÷ 240 V = 90 A of your 150 A panel
The two checks
- Circuit at the rangeRange needs 40 A at 240 V40 A works
Same size circuit. Plug it in.
- Panel90 A of 150 A with the range60 A to spare
Room for it.
Stick a fridge magnet to the bottom of each pan. If it grabs hard, it works on induction. Aluminum, copper and glass won't.
See induction-ready cookware on Amazon (opens Amazon in a new tab)As an Amazon Associate we earn from qualifying purchases.
Not sure you like induction? A single plug-in burner runs on any 120 V outlet. You can test your pans on it too.
See portable induction burners on Amazon (opens Amazon in a new tab)The install manual has the final say on breaker size. Check it before you buy wire. Some 30 in ranges want 50 A.
How we work it out
Two checks. First, the circuit at the range. Most 30 in induction ranges ask for 40 A. Most 36 in ones ask for 50 A.
breaker = nameplate kW × 1000 ÷ 240 V × 80%, rounded up to 40, 50 or 60 A
If the circuit you have is smaller, the wire has to be replaced. A bigger breaker on small wire is a fire risk. If you cook on gas now, you need a new 240 V run.
Second, the panel. We add the range to your house with the NEC 220.83 method for existing homes. The 2026 NEC moved load calcs to a new Article 120, so it's 120.83 there.
house loads = sq ft × 3 VA + 4.5 kVA kitchen and laundry circuits + appliances + range
counted = first 8 kVA + 40% of the rest + heat and AC
panel amps = counted VA ÷ 240 V
Over your main breaker is a no. Under 10 A to spare is tight. If the panel is full, a 120 V induction range with a battery inside plugs into a normal outlet.
Where the numbers come from
More calculators
- Fridge fitWill this fridge fit my opening and get through my doors?
- Dishwasher fitWill it fit under my counter?
- Freezer and wine fridge fitWill it fit, with room to breathe?
- Range hood sizerWhat CFM, width and duct do I need?
- Microwave over the rangeIs there room above my cooktop?
- Island fitWill an island fit and leave room to walk?
- Island seatingHow many stools, and what height?
- Pendant heightHow high over the island?
- Countertop slabsHow many slabs, and where do the seams go?
- Backsplash tileHow much tile for my backsplash?
- Cabinet runDo these boxes fill my wall?